Inter-Area Oscillation Damping in Data-Center-Integrated Power Systems

Ahmed Alfatlawi, Masoud H. Nazari

arXiv (eess.SY) · 2026

arXiv ↗

This paper develops explicit dynamic models of a hyperscale data center, including its heating, ventilation, and air conditioning (HVAC) and uninterruptible power supply (UPS) subsystems, and integrates them into a small-signal stability framework to investigate the impact of data center demand response on power system inter-area oscillations. Through eigenvalue analysis and time-domain simulations, the results demonstrate that UPS-based demand response can enhance inter-area oscillation damping. In contrast, the HVAC subsystem is shown to be inherently incapable of providing effective oscillation damping due to its limited thermal response bandwidth.

A gradient-based optimization algorithm is used to tune the UPS controller gain to maximize the damping ratio of the critical inter-area mode. The effectiveness of the proposed approach is validated using the IEEE 39-bus test system.

📄 이 논문을 인용한 Paperis 글

이 논문이 근거 목록에 올라 있는 Paperis 글입니다.